Capacity design (Ductility class DCM) of a light timber frame building

This work illustrates the procedure for the capacity design of a light timber frame building in ductility class DCM. It also presents a practical application to a case study: a two-storey structure is designed using the software TimberTech Buildings, of which the calculation report is totally reproduced.

Dissipative structural behaviour

Earthquake-resistant timber buildings should be designed considering either:

  • dissipative structural behaviour;
  • low-dissipative structural behaviour.

In the first concept the capability of parts of the structure (dissipative zones) to resist earthquake actions out of their elastic range is taken into account. Dissipative zones shall be located in joints and connections, whereas the timber members themselves shall be regarded as behaving elastically.

In the second concept the action effects are calculated on the basis of an elastic global analysis without taking into account non-linear material behaviour.

Ductility classes and overstrength factor

Depending on their ductile behaviour and energy dissipation capacity under seismic actions, buildings shall be assigned to one of the three following ductility classes:

  • DCH, high capacity to dissipate energy;
  • DCM, medium capacity to dissipate energy;
  • DCL, low capacity to dissipate energy.

In DCH and DCM the European standard (UNI EN 1998-1 §8.1.3) requires the use of the capacity design procedure.

The capacity design has the purpose of ensuring a ductile behaviour to the dissipative structure and operates as follows:

  • distinguishes elements and mechanisms, both local and global, into ductile and fragile;
  • aims to avoid local brittle ruptures and the activation of global brittle or unstable mechanisms;
  • aims at locating the energy dissipations by hysteresis in areas of the ductile elements identified and designed for this purpose.

To ensure the correct behaviour of the structure, the seismic resistance of the local/global brittle elements/mechanisms must be designed to be grater than that of the ductile elements/mechanisms. To ensure compliance with this inequality, both locally and globally, the strength of the ductile elements/mechanisms is increased by means of a suitable coefficient γRd known as the “overstrength factor”; starting from this increased capacity, the capacity of the brittle elements/mechanisms is sized. This coefficient is defined as equal to 1.3 for the ductility class DCM and 1.6 for the ductility class DCH.

The resistance demand evaluated with the capacity design criteria can be assumed not to exceed the strength demand evaluated for the non-dissipative structural behaviour.

Dissipative zones and non-dissipative zones

Considering a light timber frame building in ductility class DCM, the dissipative zones consist of:

  • mechanical connection between frame and cladding sheets;
  • ductile elements of the tension connection (for example the nailing);
  • ductile elements of the shear connection (for example the nailing).

The non-dissipative zones are instead represented by:

  • cladding sheets;
  • brittle elements of the tension connection (for example the concrete anchors);
  • brittle elements of the shear connection (for example the concrete anchors);
  • timber elements.

Progettazione in capacità edificio in legno

Figure 1Light timber frame building in ductility class DCM: dissipative zones

… continue reading in the PDF containing also the calculation report.

Download

Capacity design (Ductility class DCM) of a CLT building

This work illustrates the procedure for the capacity design of a CLT building. It also presents a practical application to a case study: a two-storey structure is designed using the software TimberTech Buildings, of which the calculation report is totally reproduced.

Dissipative structural behaviour

Earthquake-resistant timber buildings should be designed considering either:

  • dissipative structural behaviour;
  • low-dissipative structural behaviour.

In the first concept the capability of parts of the structure (dissipative zones) to resist earthquake actions out of their elastic range is taken into account. Dissipative zones shall be located in joints and connections, whereas the timber members themselves shall be regarded as behaving elastically.

In the second concept the action effects are calculated on the basis of an elastic global analysis without taking into account non-linear material behaviour.

Ductility classes and overstrength factor

Depending on their ductile behaviour and energy dissipation capacity under seismic actions, buildings shall be assigned to one of the three following ductility classes:

  • DCH, high capacity to dissipate energy;
  • DCM, medium capacity to dissipate energy;
  • DCL, low capacity to dissipate energy.

In DCH and DCM the European standard (UNI EN 1998-1 §8.1.3) requires the use of the capacity design procedure.

The capacity design has the purpose of ensuring a ductile behaviour to the dissipative structure and operates as follows:

  • distinguishes elements and mechanisms, both local and global, into ductile and fragile;
  • aims to avoid local brittle ruptures and the activation of global brittle or unstable mechanisms;
  • aims at locating the energy dissipations by hysteresis in areas of the ductile elements identified and designed for this purpose.

To ensure the correct behaviour of the structure, the seismic resistance of the local/global brittle elements/mechanisms must be designed to be grater than that of the ductile elements/mechanisms. To ensure compliance with this inequality, both locally and globally, the strength of the ductile elements/mechanisms is increased by means of a suitable coefficient γRd known as the “overstrength factor”; starting from this increased capacity, the capacity of the brittle elements/mechanisms is sized. This coefficient is defined as equal to 1.3 for the ductility class DCM and 1.6 for the ductility class DCH.

The resistance demand evaluated with the capacity design criteria can be assumed not to exceed the strength demand evaluated for the non-dissipative structural behaviour.

Dissipative zones and non-dissipative zones

For a CLT building in ductility class DCM, the dissipative zones consist of:

  • mechanical connections between walls;
  • ductile elements of the tension connection (for example the nailing);
  • ductile elements of the shear connection (for example the nailing).

The non-dissipative zones are instead represented by:

  • brittle elements of the tension connection (for example the concrete anchors);
  • brittle elements of the shear connection (for example the concrete anchors);
  • timber elements.

Progettazione in capacità edificio in legno

Figure 1 – CLT building in ductility class DCM: dissipative zones

… continue reading in the PDF containing also the calculation report.

Download

Ex-Marangoni: nine and five-storey buildings in XLAM

The area once occupied by the historic production site of the ex Marangoni Meccanica, in the southern area of Rovereto, is being redeveloped through the construction of a pair of nine and five-storey timber buildings, for a total of 68 apartments for social housing. Manufactured using the wood of the fir trees felled by the Vaia storm in Val di Fiemme and in Primiero, the buildings meet the modern criteria of construction, for a sustainable project from a social, environmental and economic point of view.

Structural designers: Tiziano Sartori (ReWis) and Martino Miori (XLAM Dolomiti)

More info: www.ex-marangoni.it

Clients: Heliopolis, Ri-Legno

Main sponsor: Rockwool, XLAM Dolomiti

Patronages: Habitech, ARCA, PEFC

Fire design of CLT elements. Glue line integrity maintained or not?

The check of CLT elements under fire conditions can be crucial in the design of a timber structure. Due to the layered structure of their cross-section, the calculation process is peculiar as pointed out in the examples below.

The charring depth of a CLT panel under fire conditions depends on the properties of the glue used in the panel assembly. The polyurethane glue (PUR), often used by manufacturers, is not resistant in case of high temperature meanwhile MUF glue (melamine-urea-formaldehyde) shows better performance.
This is why the new TimberTech Buildings additional module for the fire design of timber structures implements two calculation models to be applied according to the CLT properties certified by the manufacturer:

  • Glue line integrity maintained: the charring rate is assumed to be constant through the whole cross-section. This method can also be used when the manufacturer’s certificates suggest a constant charring rate (higher than that of the wood) to take into account the lower performance of the glue in a simplified manner.
  • Glue line integrity not maintained: the charring rate is not constant and depends on the panel stratigraphy. The CLT cross-section can be seen as a sequence of layers where each one acts as a protective layer for the following one. Therefore, the method for protected elements provided by EN 1995-1-2 can be applied to obtain a charring rate trend such as the one reported in the figure below where the k3 factor usually has a value of 2.

CLT Charring Rate

CLT design example: R60 with glue line integrity not maintained

CLT - Glue line integrity not maintained

  • Cross-section: 120 mm (20-30-20-30-20)
  • Glue: glue line integrity NOT maintained
  • Fire exposure: 60 minutes on one side
  • Unidimensional charring rate: beta0 = 0.65 mm/min
  • Charring depth: dchar,0 = 53 mm. Layer 1 (constant charring rate), layer 2 (double charring rate in the first 25 mm, then constant charring rate), strato 3 (double charring rate up to the required 60′)
  • Effective charring depth: def = dchar,0 + k0d0 = 60 mm
  • Effective cross-section: 60 mm (20-30-10)

 

Bending check 101% (MEd = 11.36 kNm)
Shear check 14% (VEd = 7.81 kNm)

 

Download the TimberTech Buildings calculation report about this example

Download

 

CLT design example: R60 with glue line integrity maintained

CLT - Glue line integrity maintained

  • Cross-section: 120 mm (20-30-20-30-20)
  • Glue: glue line integrity NOT maintained
  • Fire exposure: 60 minutes on one side
  • Unidimensional charring rate: beta0 = 0.65 mm/min
  • PCharring depth: dchar,0 = 39 mm. Constant charring rate through all layers
  • Effective charring depth: def = dchar,0 + k0d0 = 46 mm
  • Effective cross-section: 74 mm (20-30-20-4)

 

Bending check 55% (MEd = 11.36 kNm)
Shear check 12% (VEd = 7.81 kNm)

 

Download the TimberTech Buildings calculation report about this example

Download

 

Cross Laminated Timber (CLT) Beams Loaded in Plane: Testing Stiffness and Shear Strength

New paper by Francesco Boggian, Mauro Andreolli and Roberto Tomasi on the assessment of stiffness and shear strength of CLT beams loaded in-plane.

Set up

Abstract: Cross Laminated Timber (CLT) is a relatively new timber product used in construction that has gained popularity over the last decade. The product itself is constituted by multiple glued layers of juxtaposed boards, usually arranged in an orthogonal direction between one layer and the adjacent ones. This particular structure brings several benefits, such as the possibility to use the same product both for walls and slabs, since it can bear in-plane and out-of-plane loads. However, the mechanical behavior differs from usual timber products, and research is still ongoing to achieve common agreement on standard procedures for testing products and theories for evaluating stresses for safety verifications. This paper focuses on the in-plane shear behavior of CLT and analyzes the existing methods to evaluate shear stresses. An experimental part then presents a four-point bending test of CLT beams with a specific geometry to induce shear failure. Results are reported both for the elastic range test, measuring the Modulus of Elasticity, and for the failure test to investigate shear behavior with regard to different mechanisms. Previously exposed methods are used for the calculation of shear stresses and to analyze the correspondence between them, and the results are then compared with other existing tests and values in literature. A new test setup for future research is eventually proposed.

Failure modes

Continue…

Download the full paper

CLT multi-family residential building

Multi-family residential building with n. 8 lodgings, arranged on three levels above ground and a basement level used as a garage. The above-ground structure was build with CLT panels for walls and floors and with glulam timber beams and HEB steel beams.
Site of construction: Ischia di Pergine, Trento (TN)

Structural designer: Dr. Ing. Rossano Stefani
Architectural designer: Arch. Aldo Tomaselli
Construction company: Domus Immobiliare S.r.l.

Five floors residential buildings with framed walls

 

Residential building complex commissioned by ATER Trieste consisting of 5 buildings. Each building has 5 floors above ground plus the pitched attic floor. The walls are made with timer frames, while the floors are in CLT, including the ramps and the stairways, with the exception of the roof which is made of joists. The terraces are partially supported by steel structures.

Structural designers of the wooden structures: Ing. Sandro Rossi – Ing. Raffaele Cruciani, Ascoli Piceno, Italy

studioing-cru.ro@libero

Timber light-frame and CLT school

School complex made of three buildings separated by two seismic joints.
The strucures in elevation are made of both CLT (XLAM) panels and light frame walls. More in depth, the buildings hosting the classrooms and the locker rooms are built with structural light-frame walls while the gym building is made of CLT (XLAM) panels. Finally, the outdoor stairs are made of steel beams while the indoor stairs and the foundations are built in reinforced concrete.

Structural project: ReWis, Comano Terme (Trento)
www.rewis.it

Multi-storey residential CLT building

Multi-storey residential CLT building built in Sesto Fiorentino (Florence).
The building is made of four floors and has a maximum height of 13 m while the building base covers a 24.8 x 15.5 m rectangle.
The structure in elevation is entirely built with CLT (XLAM) panels while the basement and the foundations are made of reinforced concrete.

Structural project: ReWis, Comano Terme (Trento)
www.rewis.it